Impact of RES penetration on the frequency dynamics of the 500 kV vietnamese power system

2019

The increase of renewable energy sources (RES) typically operating as converter-interfaced generation (CIG) is progressively causing a significant change of power systems operation paradigm. The reduction of the overall available kinetic energy and the consequent impact on the dynamic response of the system is a relevant issue currently under investigation in academic and industrial scopes. The work analyzes the impact of different CIG penetration in the three areas of the 500 kV Vietnamese power system, North, Center and South. The system is modified substituting conventional synchronous generation with converter-interfaced generation. The models of power converters and corresponding contr…

Inertial responseImaginationInertial responseComputer sciencebusiness.industrymedia_common.quotation_subjectSynthetic inertiaVirtual inertiaPower electronics generationConverter-interfaced generationPenetration (firestop)ConvertersAC powerAutomotive engineeringRenewable energyVirtual inertiaSettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaElectric power systemVietnamese power systembusinessmedia_common
researchProduct

Frequency Dynamics in Fully Non-Synchronous Electrical Grids: A Case Study of an Existing Island

2022

The operation of a power system with 100% converter-interfaced generation poses several questions and challenges regarding various aspects of the design and the control of the system. Existing literature on the integration of renewable energy sources in isolated systems mainly focuses on energy aspects or steady-state issues, and only a few studies examine the dynamic issues of autonomous networks operated with fully non-synchronous generation. A lack of research can be found in particular in the determination of the required amount of grid-forming power, the selection of the number and rated power of the units which should implement the grid-forming controls, and the relative locations of …

Settore ING-IND/33 - Sistemi Elettrici Per L'EnergiaControl and OptimizationRenewable Energy Sustainability and the EnvironmentEnergy Engineering and Power Technologymicrogrids; frequency control; grid-forming; 100% converter-interfaced generation; virtual synchronous machine100% converter-interfaced generation frequency control grid-forming microgrids virtual synchronous machineElectrical and Electronic EngineeringEngineering (miscellaneous)Energy (miscellaneous)Energies
researchProduct

A Study of Power-Frequency Dynamics in Isolated Power Networks with 100% Converter-Interfaced Generation

2020

The operation of a system with 100% converter-interfaced generation poses several questions and challenges regarding various aspects of the dynamic characteristics of the system. The effects related to the power-frequency control are among the most relevant issues which need to be investigated. The paper takes into examination the case of an existing isolated power network of a geographical island assuming a completely converter-interfaced generation. The factors playing a fundamental role in the assessment of which sources should be designated to be grid-forming are identified with a small signal model formulation of a generic multiple oscillators system. Simulations and analysis performed…

Settore ING-IND/33 - Sistemi Elettrici Per L'Energiafrequency controlpower system stability100% penetrationConverter-interfaced generationvirtual synchronous machine (VSM)
researchProduct

Synthetic Inertia Impact on Inter-Area Oscillations of the Continental Europe Power System

2020

The overall kinetic energy reduction due to increasing share of converter-interfaced generation (CIG) has been investigated so far by several works for systems of different types and sizes. The so called synthetic inertia is one of the most common and reviewed solutions to the issue of system inertia reduction. The paper investigates the effects of synthetic inertia as frequency service provided by the CIG sources for the Continental Europe (CE) synchronous area using a detailed large scale dynamic model. The model - provided in the basic form by the System Protection & Dynamics (SP&D) group of the ENTSOE - is properly developed substituting a determined amount of synchronous machin…

converter-interfaced generationdynamic analysiFrequency responseinter-area oscillationComputer scienceContinental Europe020209 energymedia_common.quotation_subjectModal analysisComputationAutomatic frequency control02 engineering and technologyInertiaPower (physics)Settore ING-IND/33 - Sistemi Elettrici Per L'EnergiaElectric power systemfrequency controlControl theory0202 electrical engineering electronic engineering information engineeringsynthetic inertiaReduction (mathematics)media_common2020 IEEE PES Innovative Smart Grid Technologies Europe (ISGT-Europe)
researchProduct

Impact of Converter-Interfaced Generation to the Frequency Response of the European Power System

2019

The increase of converter-interfaced generation (CIG) typically related to renewable energy sources is progressively causing a significant change of power systems operation. The curtailment of synchronous generation with the consequent reduction of the overall kinetic energy is one of the related issues, currently under investigation in academia and industry. The work considers the problem of overall inertia reduction from a large-scale point of view, analyzing the impact of different CIG integration levels to the frequency response of the power system of Continental Europe. The kinetic energy is evaluated for each country of the synchronous area, and the system is modified substituting con…

dynamic analysiSettore ING-IND/33 - Sistemi Elettrici Per L'Energialow inertiaContinental Europefrequency responseConverter-interfaced generation
researchProduct

Impact of the high share of converter-interfaced generation on electromechanical oscillations in Continental Europe power system

2020

This study investigates the effects of converter-interfaced generation integration on the dynamic response of the power system of Continental Europe. The system is analysed with a large-scale dynamic model of the entire synchronous area, considering different instantaneous integration percentages of converter-interfaced generation across the system. The study focuses on the reduction of the overall available kinetic energy and the impact on frequency dynamics and system oscillations. The dynamic model of the system originally provided by ENTSO-E is further developed according to a specific methodology, replacing a determined amount of synchronous generation and introducing a corresponding a…

dynamic analysilow inertiaRenewable Energy Sustainability and the EnvironmentComputer scienceGeneration loss020209 energyModal analysisContinental Europe020208 electrical & electronic engineeringConverter-interfaced generation02 engineering and technologySettore ING-IND/33 - Sistemi Elettrici Per L'EnergiaElectric power systemfrequency controlWestern europe0202 electrical engineering electronic engineering information engineeringElectronic engineeringReduction (mathematics)
researchProduct